Humidity Control Strategies for Winter Conditions
By Marina Lambert, Stéphane P. Lemay, Liliane Chénard, Ernest M. Barber, Trever Crowe and published by the Prairie Swine Center - Most control systems used in swine facilities are temperature controlled, relying on a constant minimum ventilation rate (MVR) for relative humidity (RH) and contaminant controls during the cold season.Background
A survey conducted with 15 grower-finisher farms of the Prairies confirmed that conventional control systems are used and less than half the farms surveyed used recommended MVR settings. In more than half the farms, MVR adjustments were done to keep it to its minimum or to adjust it when the barn operator felt that the humidity was too high.
Underestimating MVR results in high RH and contaminant concentrations. Overestimating MVR results in higher energy cost for ventilation and supplemental heating. A system that could automatically adjust the ventilation according to the room humidity could improve the overall conditions in the building and optimize energy requirements.
Modelling
A computer model has been developed to evaluate the benefits of temperature-humidity control (THC) systems that take into account the room RH over a more conventional temperature control (TC) system. A full-scale grower-finisher room supplied with commercial equipment and control systems was simulated under Prairie winter conditions and under different control strategies.
Simulations
The comparison of heating and ventilating systems was based on average temperature,
energy demand and respective fluctuations of humidity and carbon dioxide
concentrations. For THC systems, Proportional (P) and Proportional-Integral-Derivative
(PID) controls were simulated from November through March under Saskatchewan
winter conditions. Based on simulations, a TC system provides effective humidity control
considering that the minimum ventilation rate is adequately set and adjusted throughout
the growth period.
Figure 1 presents the RH obtained with three specific strategies: TC;
THC with a PID control and a RH setpoint of 77 per cent; and THC with a P control with
a 75 per cent setpoint and a 5 per cent PBand. As shown on Fig. 1, THC strategies
keep the RH at the setpoint approximately 30 per cent of the time. A much wider
variability is obtained with TC strategy. Furthermore, THC strategies are more
appropriate as the ventilation is being adjusted to the room moisture production that can
fluctuate within a day or as a result of sporadic water wastage. In THC control,
decreasing the setpoint from 80 to 70 per cent increases energy requirements by a
factor of two.
For a given RH setpoint, PID control requires more energy than P control
as it keeps the RH at that setpoint or lower. However when equivalent RH conditions
are maintained (75 per cent setpoint with P control and 77 per cent setpoint with PID
control), energy requirements are similar or lower with PID control as shown in Fig. 2
and Table I.
Optimum strategy
Overall with specific setpoints, PID (77 per cent) compared to P control (75 per cent-5 per cent) provides higher RH and CO2 concentrations but differences are lower than 2.5 per cent. Considering simulation results, the controller complexity, the expected accuracy of those controller and humidity sensors, the strategy selected as being optimum was THC with P control, a 75 per cent RH setpoint and a proportional band of 5 per cent (THC-P-75 per cent-5 per cent P. Band).
Acknowledgements
The authors wish to acknowledge the funding provided for this project by the Natural
Sciences and Engineering Research Council of Canada, Agriculture and Agri-Food
Canada, TDK Corporation of America and DelAir Systems Ltd. The project was initiated
by Drs. Y. Zhang and A. Tanaka and their foresight in starting the project and getting it
funded are appreciated. Strategic funding was provided by SaskPork, Alberta Pork,
Manitoba Pork, and Saskatchewan Agriculture and Food Development Fund.
Source: Prairie Swine Centre - January 2006